Discover datacenters / United Kingdom
Level(3) London (Goswell Road)
Lumen Technologies Inc · London · London Metro · United Kingdom
- Design resilience tier
- III
- Redundancy (as published)
- UPS 1 - 3x 500kVA modules — UPS 2 - 4x 625kVA modules — UPS 3 - 3x 625kVA modules (undergoing upgrade) — UPS 4 - 3x500kVA modules — UPS 7 - 3x 550kVA modules — Five separate UPS systems as above of both Hybrid Rotary UPS modules and static modules providing approx 9000kVA output each with N+1 redundancy — Total facility UPS capacity 9500kVA N+1 — 15-Minute battery autonomy per UPS module — Dual redundant A&B distribution strategy - Underfloor power track distribution system — Dual redundant 4MVA, 11kV dedicated underground cable feeds to dedicated dual redundant 4MVA transformer station — 4 x 4.3MVA diesel driven emergency power generators giving 4MVA — Automatic start in less than one minute to feed 100% of the facility — Fuel storage (diesel) for 24-hour continuous operation at 100% load (Lumen-factsheet LEN1228, (c)2021)
- Availability
- Availability on request
- Cross-connect
- On request
Data trust
- Availability
- Imported · Recorded 08 Jun 2026 · Not recent
ColocationConnectivityISO 27001ISO 50001
Need a quote or an introduction? One request, with a response within two business days.
Request a quoteDo you manage this datacenter? This profile is based on public sources. Claim this listing — free — and keep the data current yourself.