Discover datacenters / Germany
InterNetX Data Center
InterNetX GmbH · München · Munich Metro · Germany
- Design resilience tier
- III
- Redundancy (as published)
- Building power connection by means of two residual-current-monitored 10KV underground cables, redundancy n+2; AC UPS with bridging time of more than 15 minutes; concept with diesel generators, two feeds each with 3200A circuit breaker; separate head distributions (PDUs) per A and B customer distribution; separate A/B busbar system for supplying the critical equipment and the non-critical systems; redundant fibre feed by different suppliers for the physical access lines; data centres are redundantly connected; Tier 3 classification; EN 50600: availability class VK3, protection class SK 1-4, energy efficiency GN3. Housing brochure: redundantly designed air conditioning and power supply; secure power supply and standby power plant (diesel generator set); multiply redundant internet connection.
- Floor area
- 1,100 m² whitespace
- Security
- 24/7 on-site security
- Year built
- 2006
- Cooling
- Air cooling
- Availability
- Available
Platform reviewed · 03 Sept 2026 · Recent
- Cross-connect
- On request
- Renewable power
- 100% renewable power
- Services
- Colocation, connectivity and cloud and managed services
- Certifications 3
- ISO 27001ISO 9001EN 50600
Location
View on the full map · 2 locations at this address · Elevation 507 m above sea level

Interested in this location? Send one inquiry with your requirements and receive a response within one business day.
Data sources
This profile is based on public sources; the operator has not yet confirmed its data. Confirmed data carries the Verified badge and a confirmation date.
Do you manage this datacenter? Claim your listing at no cost and keep the data current yourself.