- Design resilience tier
- III
- Redundancy (as published)
- Power: 5 transformateurs (3x1.6 MW + 2x1.25 MW), 2 GE de 1.6 MW, Onduleurs 2x1200 kVA, Salles raccordées en 2N. Cooling: 20 unités DX freecooling 2N, double circuit condensation 3 MW.
- Cooling
- Liquid-ready
- Availability
- Availability on request
- Cross-connect
- On request
- Design PUE
- Design PUE 1.2–1.4