- Design resilience tier
- III
- Redundancy (as published)
- Location Data Sheet 03-2026: "Designed to a Colt tier 3 specification"; "N+2 cooling units"; "150MVA x 2 power transformers in N+N configuration"; "N+N redundancy on EHV power supply"; "Backed up by dedicated Uninterrupted Power Supply (UPS)". Datasheet 06-2020: "Electrical – Static UPS in a distributed redundant N+1 configuration"; "Mechanical – Packaged DX in an N+1 configuration"; "Diversely fed A+B utility w dedicated on site sub at 220kV"
- Security
- 24/7 on-site security
- Density (as published)
- Datasheet 06-2020: "Power densities up to 3.0kW/m2 (7.5kW/rack average)"; "up to 1.50MW IT per 500m2"
- Power band
- 20–50 MW
Platform research · Recorded 06 Oct 2026 · Recent
- Cooling
- Air cooling
- Availability
- Availability on request
Imported · Recorded 08 Jun 2026 · Not recent
- Cross-connect
- On request
- Renewable power
- 100% renewable power
- Design PUE
- Design PUE 1.4 to 1.6
- PUE note
- Annualised PUE of 1.45; an older datasheet gave below 1.40.
- Services
- Colocation and wholesale
- Certifications 1
- ISO 27001