Discover datacenters / Switzerland
Brainserve
BrainServe SA · Crissier · Regional Switzerland · Switzerland
- Design resilience tier
- IV
- Redundancy (as published)
- Double electrical grid with transparent switching < 10 ms using load transfer modules (STS). Each rack is connected via energy rails to 2 separate electric control panels (redundancy N+N). Each electric distribution branch is protected by dynamic kinetic-energy accumulation inverters (5 x 2'500 kVA NoBreaks, N+1 redundancy). Each electric distribution branch is protected by a diesel generator (5 x 2'500 kVA generators directly connected to the dynamic inverters, N+1 redundancy). Cooling: 4 x 2'500 KW turbo groups (redundancy N+N), 2 free cooling exchangers. Double iced water distribution network (redundancy N+N). Air-conditioning units: 50 KW per unit for liquid cooling (redundancy N+N), 55 KW per unit for the aeraulic cooling (N+1 redundancy).
- Rack density
- from 4 kW/rack
- Density (as published)
- between 4'000 W and 12'000 W per rack on average; this power can be increased according to the fitting out of the housing area
- Cooling
- Free cooling, Liquid-ready
- Availability
- Availability on request
- Cross-connect
- On request